The CELLTRON™ Ultra provides advanced battery testing capabilities for stationary batteries used in UPS systems, power utility, telecommunications industries and is ideal for use in data centers or other environments with high levels of electrical interference noise.
- Description
Description
Applications
- Tests individual lead acid cells or monoblocs (up to 16 Volts) in any common configuration, approximately 10-6000 Ah
Test Data Storage
- 500 string locations of 480 test results per string stored internally
User Programmable Functions
- Preset values for over 250 battery types
- Low voltage alarm setting
- Low conductance warning
- Low conductance alarm
- Test mode (pushbutton/auto start)
Calibration
- Franklin Electric Grid Solutions will work with each customer to establish a regular calibration program if it is required by their quality or other management systems
Connectorized Test Cable Options
- Dual contact clamps
- Dual contact probes
- Custom cables by quotation
Power Requirements
- 9.6V, 1600mAH, NiMH
- Internal swappable battery & charger
LCD – FSTN Display
- 2.619 in x 1.309 in
- 128 x 64 pixels
- 40 degree viewing angle
- Contrast ratio 8
- Green LED backlight
Keypad
- Stainless-steel dome
- Polycarbonate overlay
- 1,000,000 actuations
Data Transfer
- Infra-red HP protocol
- Infra-red
- Half-duplex IRDA protocol
- RS-232 printer
- Secure digital card
Environmental Operating Range
- 0 to +104°F (0 to +40°C)
- 95% relative humidity
- Non-condensing
Over Voltage Protection
- Auto-reset disconnect
- Reverse polarity protected
Housing Material
- Acid-resistant ABS plastic
- Santoprene™ overmold
Voltage Range | 1.5 – 20.0 Volts DC |
Conductance Range | 100 – 19,990 Siemens |
Accuracy | + 2% across test range |
Voltmeter Resolution | 5mV |
Storage Temperature | -4 to 180°F (-20 to 82°C) |
Analyzer Dimensions | 11in x 4in x 3in (279mm x 105mm x 80mm) |
Analyzer Weight | 2.6 lb (1 Kg) |
Case Dimensions | 19in x 15.5in x 7in (485mm x 395mm x 180mm) |